| Sources
of natural light and ventilation |
|
54. |
Every room in any building shall be provided with natural light and ventilation
by means of one or more sources having an aggregate area of not less than- |
|
Rooms
for residential purposes
|
|
| (a) |
15 per cent of the floor
space of the room of which atleast 70 per cent shall have openings so as to allow
free uninterrupted passage of air, if such room is used for residential purposes
[(excluding such room as referred to in paragraph (c)], |
|
| If
such room is in a low rise building there should be an-unobstructed passage of
not less than 2.3 m. between such opening and the boundary of the lot opposite
to such opening. |
| Rooms
for business purposes, etc.
|
|
| (b)
| 15
per cent of the floor space of the room of which at least 50% shall have openings
so as to allow free uninterrupted passage of air, if such room is used for business
purposes or in connection with a shop, a place of public resort, a factory or
any other usage not mentioned in this regulation; |
|
Storces,
garages, etc in residential buildings.
|
|
| (c) |
10% of the floor space
of the room of which 50% shall have openings so as to allow free uninterrupted
passage of air, if such room is used as a store, pantry , utility room, garage
or the like in a residential building. |
|
Water
closets toilets and bathrooms
|
|
| (d)
| 10%
of the floor space of the room or 0.2 m2 (whichever is greater) of which 100%
shall have openings so as to allow free uninterrupted passage of air, if such
room is a water-closet, latrine, urinal, bathroom, toilet or laundry room; |
|
Schools
|
|
| (e).
| 20%
of the floor space of the room of which at least 50 per cent shall haveopenings
so as to allow free uninterrupted passage of air, if such room is used for the
dissemination of knowledge in school;
|
|
| (f). |
20% of the floor space
of the room of which 100% shall have openings so as to allow free uninterrupted
passage of air, if such room is used for the accommodation of patients in a hospital,
convalescence home, nursing home or the like; |
|
Staircase,
corridors and lobby
|
|
| (g) |
10% of the floor area per
floor in the case of an enclosed staircase, corridor or lobby of which 50 per
cent shall have openings so as to allow a free uninterrupted passage of air except
as required under the provisions of the Code of Fire Precautions for Buildings.
|
| Parking
|
|
| (h) |
10% of the floor space of
the room of which at least 50% shall have openings so as to allow free uninterrupted
passage of air |
|
Factories,
warehouses and godowns
|
|
| (i)
| 10%
of the floor space of the room of which atleast 50 per cent shall have openings
so as to allow free uninterrupted passage of air, if such room is used as a godown
or any other storage area. |
|
Terrace
Houses
|
| 55.
| In
addition to the requirements of paragraph (a) of regulation 57 there shall also
be provided in the case of terrace houses of a depth greater than 12 m. permanent
ventilation from front to rear by suitable vents in all front, back and cross
walls at each floor. Such vents shall have a net opening area of not less than
0.4 square meters. |
|
Adjoining
rooms
|
|
56. |
For the purpose of determining
light and ventilation requirements, any room may be considered as a portion of
an adjoining room when half of the area of the common wall is open and unobstructed |
|
Natural
light and ventilation for basement rooms
|
|
57. |
When any room is located
in a basement and is to be naturally lighted and ventilated, such room shall have
atleast one third of the height of its external walls and all its required sources
of natural light and ventilating above the outside ground level. |